SILMET PVC GAS, a copper tube pre-insulated with PVC used for gas distribution. It is produced with cutting-edge machinery, in compliance with all the international reference standards and manufactured according to Presidential Decree no. 1095/68 and Ministerial Decree no. 174 of 6 April 2004 of the Italian Department of Health - ref. European Council Directive no. 98/83/EC regarding the transport of drinking water and suitable for building gas distribution plants (UNI CIG 7129).
Characteristics
It is coated with a yellow polyvinyl chloride (PVC) sheath that makes it easy to recognise during installation; it is non-toxic, odourless and free from chlorofluorocarbons (CFCs).
The characteristics of our coating in PVC GAS make the copper tube resistant to abrasions and corrosion and the particular internal structure allows its correct expansion without jeopardising the condition of the coating.
The PVC coating is odourless, non-toxic and is made without the use of CFCs. It is suitable to be used in plants with operating temperatures ranging from -80°C to +100°C.
The PVC GAS copper tube is supplied in 50-metre coils (25 metres with Ø 22 mm) marked at intervals also indicating the relative metres.
The main characteristics of the PVC GAS sheath are excellent plasticity, mechanical resistance to abrasions and corrosion, all ensuring that the tube lasts for a long time. Perfect adherence to the tube without insulation: the coating complies with UNI 10823 "Coated copper tubes for gas application in underground zones".
Supply
The copper tube EN 1057 is marked СЄ as required by EU 305/2011 EU Construction Products Regulation (CPR).
THICKNESS OF THE INSULATING SHEATH | 2 mm |
USAGE TEMPERATURES | -80 °C +100 °C |
THERMAL CONDUCTIVITY | 0,0397 W · m-1 · K-1 |
RESISTANCE TO FIRE | Class 1 (self-extinguishing) |
WRAPPING | coils individually wrapped with transparent film for further protection |
Usage and Directives
PVC GAS copper tube is suitable for the following fields of use and with the following references:
Distribution of liquid and gaseous fuels
UNI CIG 7129
Gas systems for the household and similar powered by the distribution network - Design and installation.
Technical sheets
Alloy | Cu-DHP CW024A (Cu = 99,90% min. - P = 0,015 ÷ 0,040%) |
Physical state | Annealed |
Unit tensile strength | 220 MPa/mm2 min. |
Percentage elongation | 40% min. |
Internal cleanliness | C max. 0,20 mg/dm2 |
Dimensions and tolerances | In compliance with standard EN 1057 |
Internal surface roughness | RA 1/10 di micron |
Linear thermal expansion coefficient | 0,00168 mm/m °C |
Thermal conductivity at 20° | 364 W/m · K |
dimensions without insulation | dimensions with insulation | thickness of insulating sheath | bursting pressure | operating pressure | coil length | water content per meter |
mm | mm | mm | MPa | MPa | m | l/m |
10 X 1 | 14 | 2 | 44,88 | 11,22 | 50 | 0,0503 |
12 X 1 | 16 | 2 | 37,4 | 9,35 | 50 | 0,0785 |
14 X 1 | 18 | 2 | 32,06 | 8,01 | 50 | 0,1131 |
15 X 1 | 19 | 2 | 29,92 | 7,48 | 50 | 0,1327 |
16 X 1 | 20 | 2 | 28,05 | 7,01 | 50 | 0,1539 |
18 X 1 | 22 | 2 | 24,93 | 6,23 | 50 | 0,2011 |
22 X 1,5 | 26 | 2 | 30,6 | 7,65 | 25 | 0,2835 |
dimensions Ø x thickness | coil length | coils per pallet | meters per pallet | approx. gross pallet weight | dimensions of pack |
mm | m | n | m | kg | cm |
10 X 1 | 50 | 30 | 1.300 | 350 | h 220 X Ø 80 |
12 X 1 | 50 | 30 | 1.300 | 400 | h 220 X Ø 80 |
14 X 1 | 50 | 27 | 1.350 | 545 | h 220 X Ø 80 |
15 X 1 | 50 | 26 | 1.100 | 400 | h 220 X Ø 80 |
16 X 1 | 50 | 25 | 1.250 | 600 | h 220 X Ø 80 |
18 X 1 | 50 | 23 | 1.000 | 480 | h 220 X Ø 90 |
22 x 1,5 | 25 | 26 | 500 | 400 | h 220 X Ø 90 |
The packs cannot be stacked.
A maximum of 2 packs with a large diameter (h 220 x Ø 90 cm) and available for other coated products, are loaded onto the pallet side-by-side together with a third smaller pallet.
The others can be loaded side-by-side in threes.